CHAPTER 5
Ladder diagram
Introduction
5.1 Ladder diagram
5.2 Normally open and normally closed contacts
5.3 Brief example
Introduction
Programmable controllers are generally programmed in ladder diagram (or
"relay diagram") which is nothing but a symbolic representation of electric
circuits. Symbols were selected that actually looked similar to schematic
symbols of electric devices, and this has made it much easier for
electricians to switch to programming PLC controllers. Electrician who has
never seen a PLC can understand a ladder diagram.
5.1 Ladder diagram
There are several languages designed for user communication with a PLC,
among which ladder diagram is the most popular. Ladder diagram consists of
one vertical line found on the left hand side, and lines which branch off to
the right. Line on the left is called a "bus bar", and lines that branch off
to the right are instruction lines. Conditions which lead to instructions
positioned at the right edge of a diagram are stored along instruction
lines. Logical combination of these conditions determines when and in what
way instruction on the right will execute. Basic elements of a relay diagram
can be seen in the following picture.

Most instructions require at least one operand, and often more than one.
Operand can be some memory location, one memory location bit, or some
numeric value -number. In the example above, operand is bit 0 of memory
location IR000. In a case when we wish to proclaim a constant as an operand,
designation # is used beneath the numeric writing (for a compiler to know it
is a constant and not an address.)
Based on the picture above, one should note that a ladder diagram consists
of two basic parts: left section also called conditional, and a right
section which has instructions. When a condition is fulfilled, instruction
is executed, and that's all!

Picture above represents a example of a ladder diagram where relay is
activated in PLC controller when signal appears at input line 00. Vertical
line pairs are called conditions. Each condition in a ladder diagram has a
value ON or OFF, depending on a bit status assigned to it. In this case,
this bit is also physically present as an input line (screw terminal) to a
PLC controller. If a key is attached to a corresponding screw terminal, you
can change bit status from a logic one status to a logic zero status, and
vice versa. Status of logic one is usually designated as "ON", and status of
logic zero as "OFF".
Right section of a ladder diagram is an instruction which is executed if
left condition is fulfilled. There are several types of instructions that
could easily be divided into simple and complex. Example of a simple
instruction is activation of some bit in memory location. In the example
above, this bit has physical connotation because it is connected with a
relay inside a PLC controller. When a CPU activates one of the leading four
bits in a word IR010, relay contacts move and connect lines attached to it.
In this case, these are the lines connected to a screw terminal marked as 00
and to one of COM screw terminals.
5.2 Normally open and normally closed contacts
Since we frequently meet with concepts "normally open" and "normally closed"
in industrial environment, it's important to know them. Both terms apply to
words such as contacts, input, output, etc. (all combinations have the same
meaning whether we are talking about input, output, contact or something
else).
Principle is quite simple, normally open switch won't conduct electricity
until it is pressed down, and normally closed switch will conduct
electricity until it is pressed. Good examples for both situations are the
doorbell and a house alarm.
If a normally closed switch is selected, bell will work continually until
someone pushes the switch. By pushing a switch, contacts are opened and the
flow of electricity towards the bell is interrupted. Of course, system so
designed would not in any case suit the owner of the house. A better choice
would certainly be a normally open switch. This way bell wouldn't work until
someone pushed the switch button and thus informed of his or her presence at
the entrance.
Home alarm system is an example of an application of a normally closed
switch. Let's suppose that alarm system is intended for surveillance of the
front door to the house. One of the ways to "wire" the house would be to
install a normally open switch from each door to the alarm itself (precisely
as with a bell switch). Then, if the door was opened, this would close the
switch, and an alarm would be activated. This system could work, but there
would be some problems with this, too. Let's suppose that switch is not
working, that a wire is somehow disconnected, or a switch is broken, etc.
(there are many ways in which this system could become dysfunctional). The
real trouble is that a homeowner would not know that a system was out of
order. A burglar could open the door, a switch would not work, and the alarm
would not be activated. Obviously, this isn't a good way to set up this
system. System should be set up in such a way so the alarm is activated by a
burglar, but also by its own dysfunction, or if any of the components
stopped working. (A homeowner would certainly want to know if a system was
dysfunctional). Having these things in mind, it is far better to use a
switch with normally closed contacts which will detect an unauthorized
entrance (opened door interrupts the flow of electricity, and this signal is
used to activate a sound signal), or a failure on the system such as a
disconnected wire. These considerations are even more important in
industrial environment where a failure could cause injury at work. One such
example where outputs with normally closed contacts are used is a safety
wall with trimming machines. If the wall doors open, switch affects the
output with normally closed contacts and interrupts a supply circuit. This
stops the machine and prevents an injury.
Concepts normally open and normally closed can apply to sensors as well.
Sensors are used to sense the presence of physical objects, measure some
dimension or some amount. For instance, one type of sensors can be used to
detect presence of a box on an industry transfer belt. Other types can be
used to measure physical dimensions such as heat, etc. Still, most sensors
are of a switch type. Their output is in status ON or OFF depending on what
the sensor "feels". Let's take for instance a sensor made to feel metal when
a metal object passes by the sensor. For this purpose, a sensor with a
normally open or a normally closed contact at the output could be used. If
it were necessary to inform a PLC each time an object passed by the sensor,
a sensor with a normally open output should be selected. Sensor output would
set off only if a metal object were placed right before the sensor. A sensor
would turn off after the object has passed. PLC could then calculate how
many times a normally open contact was set off at the sensor output, and
would thus know how many metal objects passed by the sensor.
Concepts normally open and normally closed contact ought to be clarified and
explained in detail in the example of a PLC controller input and output. The
easiest way to explain them is in the example of a relay.

Normally open contacts would represent relay contacts that would perform a
connection upon receipt of a signal. Unlike open contacts, with normally
closed contacts signal will interrupt a contact, or turn a relay off.
Previous picture shows what this looks like in practice. First two relays
are defined as normally open , and the other two as normally closed. All
relays react to a signal! First relay (00) has a signal and closes its
contacts. Second relay (01) does not have a signal and remains opened. Third
relay (02) has a signal and opens its contacts considering it is defined as
a closed contact. Fourth relay (03) does not have a signal and remains
closed because it is so defined.
Concepts "normally open" and "normally closed" can also refer to inputs of a
PLC controller. Let's use a key as an example of an input to a PLC
controller. Input where a key is connected can be defined as an input with
open or closed contacts. If it is defined as an input with normally open
contact, pushing a key will set off an instruction found after the
condition. In this case it will be an activation of a relay 00.
If input is defined as an input with normally closed contact, pushing the
key will interrupt instruction found after the condition. In this case, this
will cause deactivation of relay 00 (relay is active until the key is
pressed). You can see in picture below how keys are connected, and view the
relay diagrams in both cases.

Normally open/closed conditions differ in a ladder diagram by a diagonal
line across a symbol. What determines an execution condition for instruction
is a bit status marked beneath each condition on instruction line. Normally
open condition is ON if its operand bit has ON status, or its status is OFF
if that is the status of its operand bit. Normally closed condition is ON
when its operand bit is OFF, or it has OFF status when the status of its
operand bit is ON.
When programming with a ladder diagram, logical combination of ON and OFF
conditions set before the instruction determines the eventual condition
under which the instruction will be, or will not be executed. This
condition, which can have only ON or OFF values is called instruction
execution condition. Operand assigned to any instruction in a relay diagram
can be any bit from IR, SR, HR, AR, LR or TC sector. This means that
conditions in a relay diagram can be determined by a status of I/O bits, or
of flags, operational bits, timers/counters, etc.
5.3 Brief example
Example below represents a basic program. Example consists of one input
device and one output device linked to the PLC controller output. Key is an
input device, and a bell is an output supplied through a relay 00 contact at
the PLC controller output. Input 000.00 represents a condition in executing
an instruction over 010.00 bit. Pushing the key sets off a 000.00 bit and
satisfies a condition for activation of a 010.00 bit which in turn activates
the bell. For correct program function another line of program is needed
with END instruction, and this ends the program.

The following picture depicts the connection scheme for this example.

|